Copper tubes of simple construction

Purpose: For cables and conductors with Cu-strands without longitudinal loading, the cable diameter may not occupy more than 95% of the cross-section of the gland. Suitable for the connection of earthing conductors. For higher loads, we recommend the more robust DIN tubes, e.g. KU-ZE-V.
Voltage: up to 1 kV;
Material: electrotechnical copper;
Surface: electrochemically tinned.
Recommended tools for pressing:
HN 1 0,25-10mm²
HN 5 10-16mm² ;
K 05 6-50 mm²;
K 06 10-120 mm²;
K 09 25-150 mm²;
TN 70 SE 10-70 mm²;
TN 120 SE 10-120 mm².
Special non-DIN dies are required for pressing this type of acorn.




    Name Conductor cross-section, mm² Conductor diameter, mm (rm/sm) Conductor diameter, mm (re) D, mm d, mm l, mm
    1.5 KU-L-KR 0.25-1.5 1.4 1.0 3.2 1.6 15
    2.5 KU-L-KR 1.5-2.5 2.0 1.5 3.9 2.3 15
    4 KU-L 4-6 3.0 2.5 5.6 3.6 22
    6 KU-L 6 3.0 2.75 6.5 3.5 25
    10 KU-L 10 4.1 3.25 7.0 4.5 30
    120 KU-L 120 12.5-13.5 19.5 15.0  65
    185 KU-L 185 15.8-16.8 24.0 19.0  80
    240 KU-L 240 17.8-19.2 26.0 21.0  90

    Other sizes on request (KU-L long, KU-L-KR short).
    Designations used: rm-round polyhedron; sm-sectoral polyhedron; re-uniform round monolith; se-uniform sectoral monolith.