Gerhard Petri Vilnius UAB

Nexans
e-paslaugos

Compression tubes for lines without longitudinal load, DIN 46267, Part 1

Application: for copper conductors according to DIN 48201 and copper cables according to VDE 0295. For cables without longitudinal load and with insulation of the same construction.
Voltage: 1 kV (up to 10 kV if special couplings are used);
Material: electrotechnical copper;
Surface: electrochemically tinned KU-ZE-V, uncoated KU-ZE.




    Name Conductor cross-section, mm² Conductor Ø, mm according to VDE 0295 (L. Ø according to DIN 48201/1 re/rm) Matrix code D, mm d, mm l, mm Number of clamping points (mech.) Number of clamping points (hidr.)
    6 KU-ZE-V 6 (2.75/3.2) 5 5.5 3.8 30 2-2
    10 KU-ZE-V 10 (3.55/4.1) 6 6.0 4.4 30 2-2
    16 KU-ZE-V 16 (4.5/5.1) 8 8.5 5.5 50 2-2 1-1
    25 KU-ZE-V 25 5.6-6.5(-/6.3) 10 10.0 7.0 50 2-2 1-1
    35 KU-ZE-V 35 6.6-7.5(-/7.5) 12 12.5 8.2 50 2-2 1-1
    50 KU-ZE-V 50 7.7-8.6(-/9.0) 14 14.5 10.0 56 3-3 1-1
    70 KU-ZE-V 70 9.3-10.2(-/10.5) 16 16.5 11.5 56 3-3 1-1
    95 KU-ZE-V 95 11.0-12.0(-/12.5) 18 19.0 13.5 70 4-4 2-2
    120 KU-ZE-V 120 12.5-13.5(-/14.0) 20 21.0 15.5 70 4-4 2-2
    150 KU-ZE-V 150 13.9-15.0(-/15.8) 22 23.5 17.0 80 4-4 2-2
    185 KU-ZE-V 185 15.5-16.8(-/17.5) 25 25.5 19.0 85 4-4 2-2
    240 KU-ZE-V 240 17.8-19.2(-/20.3) 28 29.0 21.5 90 5-5 2-2
    300 KU-ZE-V 300 20.0-21.6(-/22.5) 32 32.0 24.5 100 2-2
    400 KU-ZE-V 400 22.9-24.6 38 38.5 26.0 150 3-3
    500 KU-ZE-V 500 25.7-27.6 42 42.0 29.0 160 3-3
    625 KU-ZE-V 625 (-/32.6) 44 44.0 34.5 160 3-3

    Conductors with a sectoral profile must be rounded before pressing. Non-DIN tubing can also be ordered: 400 KU-ZE-S(-V), 500 KU-ZE-S(-V). These products must only be used for compacted Cu conductors. Other sizes are available on request.
    Designations used: rm-round multi-wire; sm-sector multi-wire; re-uniform round monolith; se-uniform sector monolith.