OCP2-12
By IEC 60099-4 version 2.0
Polymer housing
Uc spectrum: 3-29 kV
Rated discharge current (In; 8/20 µs): 10 kA
Linear discharge class: 2
High voltage pulse (4/10 µs): 100 kA
Energy absorption capacity:
Linear discharge pulse 6.0 kJ/kV-Uc
Long-term voltage pulse (2000 µs): 530 A
Long-term operating voltage Uc: 12 kV
Rated voltage Ur: 15 kV
OCP2-12
| Housing parameters | Measuring units | S | L |
|---|---|---|---|
| Impulse voltage 1,2/50 µs | kV | 145 | 165 |
| Industrial frequency voltage | kV | 47 | 57 |
| Height (H) | mm | 183 | 220 |
| Overlap distance | mm | 176 | 214 |
| Leakage path length | mm | 380 | 505 |
| Weight | kg | 1,8 | 2,2 |
| Number of skirts | 5 | 7 | |
| Bending resistance* | Nm | 350 | 350 |
| Resistance to pulling | N | 2000 | 2000 |
| Max. torque M12* | Nm | 50 | 50 |
* Based on “Thermomechanical and bending moment test IEC 60099-4”
| Residual voltage (kV) | |||||
|---|---|---|---|---|---|
| Lightning current pulse 8/20 µs: | Steady lightning current pulse 1/20 µs: | Switching current pulse 30/60 µs: | |||
| 5 kA | 10 kA | 20 kA | 10 kA | 125 A | 500A |
| 36,7 | 38,0 | 43,4 | 40,4 | 29,5 | 31,1 |