Gerhard Petri Vilnius UAB

Nexans
e-paslaugos

12 kV Class 2 outdoor type surge arresters

OCP2-12

By IEC 60099-4 version 2.0
Polymer housing
Uc spectrum: 3-29 kV
Rated discharge current (In; 8/20 µs): 10 kA
Linear discharge class: 2
High voltage pulse (4/10 µs): 100 kA
Energy absorption capacity:
Linear discharge pulse 6.0 kJ/kV-Uc
Long-term voltage pulse (2000 µs): 530 A
Long-term operating voltage Uc: 12 kV
Rated voltage Ur: 15 kV




    OCP2-12

    Housing parameters Measuring units S L
    Impulse voltage 1,2/50 µs kV 145 165
    Industrial frequency voltage kV 47 57
    Height (H) mm 183 220
    Overlap distance mm 176 214
    Leakage path length mm 380 505
    Weight kg 1,8 2,2
    Number of skirts 5 7
    Bending resistance* Nm 350 350
    Resistance to pulling N 2000 2000
    Max. torque M12* Nm 50 50

    * Based on “Thermomechanical and bending moment test IEC 60099-4”

    Residual voltage (kV)
    Lightning current pulse 8/20 µs: Steady lightning current pulse 1/20 µs: Switching current pulse 30/60 µs:
    5 kA 10 kA 20 kA 10 kA 125 A 500A
    36,7 38,0 43,4 40,4 29,5 31,1