RDA-12
Zinc-oxide surge arrester (according to IEC 99-4 standard)
Polymer housing
Rated discharge current: 10 kA
Linear discharge class: 1
High voltage pulse (4/10 µs): 100 kA
Energy absorption capacity:
High current pulse : 5.3 kJ/kV Uc
Linear discharge pulse: 2,6 kJ/kV Uc
Long-term operating voltage Uc: 12 kV
Rated voltage Ur: 15 kV
Suitable for indoor type applications, used with RICS crank adaptors.
Rated short-circuit current: 16 kA
Impulse current 1,2/50 µs: 52,4 kV
Industrial frequency voltage: dry surface: 22,2 kV
Weight: 2.2 kg
SPA-12
Zinc-oxide surge arrester (according to IEC 99-4 standard)
Polymer housing
Rated discharge current: 10 kA
Linear discharge class: 1
High voltage pulse (4/10 µs): 100 kA
Energy capacity:
High voltage pulse: 5.3 kJ/kV Uc
Linear discharge pulse: 2,6 kJ/kV Uc
Long-term operating voltage Uc: 12 kV
Rated voltage Ur: 15 kV
Rated short-circuit current: 16 kA
RDA-12
Residual voltage (kV) | ||||||
---|---|---|---|---|---|---|
Lightning current pulse 8/20 µs: | Steady lightning current pulse 1/20 µs: | Commutation current pulse 30/60 µs: | ||||
5 kA | 10 kA | 20 kA | 40 kA | 10 kA | 125 A | 500 A |
37,2 kV | 40,0 kV | 44,9 kV | 52,4 kV | 43,6 kV | 27,5 kV | 29,6 kV |
SPA-12
Housing parameters | |
---|---|
Resistance to bending, Nm | 200 |
Resistance to pulling, N | 1000 |
Max. torque M12, Nm | 58 |
Impulse voltage 1,2/50 µs, kV | 52,4 |
Industrial frequency voltage: dry surface, kV | 22,2 |
Leakage path length, mm | 169 |
Weight, kg | 1,9 |
Residual voltage (kV) | ||||||
---|---|---|---|---|---|---|
Lightning current pulse 8/20 µs: | Steady lightning current pulse 1/20 µs: | Commutation current pulse 30/60 µs: | ||||
5 kA | 10 kA | 20 kA | 40 kA | 10 kA | 125 A | 500 A |
37,2 kV | 40,0 kV | 44,9 kV | 52,4 kV | 43,6 kV | 27,5 kV | 29,6 kV |