Purpose: For cables and conductors with Cu-strands without longitudinal load, the cable diameter may not cover more than 95% of the cross-section of the nozzle. Suitable for connection of earthing conductors. We recommend the more robust DIN-standard lugs for higher loads, e.g. KU-V.
Voltage: up to 1 kV;
Material: electrotechnical copper according to DIN 40500;
Surface: electrochemically tinned.
KU-L: without inspection hole;
KU-L-S: with a pilot hole.
Recommended tools for pressing:
HN 5 (10-16 mm²);
K 05 (6-50 mm²);
K 06 (10-120 mm²);
K 09 (25-150 mm²);
TN 70 SE (10-70 mm²);
TN120 SE (10-120 mm²).
Name | Conductor cross-section, mm² (re/rm/sm) | Conductor diameter (rm/sm)/re, mm DIN 48201/1 | D, mm | d, mm | a, mm | l, mm | b, mm | Fixing screw M, mm |
---|---|---|---|---|---|---|---|---|
1.5×4 KU-L | 1.5 | 3.3 | 1.8 | 6.0 | 13.0 | 6.5 | 4.3 | |
1.5×5 KU-L | 1.5 | 3.3 | 1.8 | 6.0 | 13.5 | 7.5 | 5.3 | |
1.5×6 KU-L | 1.5 | 3.3 | 1.8 | 6.0 | 14.0 | 9.0 | 6.4 | |
2.5×4 KU-L | 2.5 | 4.2 | 2.4 | 6.0 | 14.0 | 7.5 | 4.3 | |
2.5×5 KU-L | 2.5 | 4.2 | 2.4 | 6.0 | 14.0 | 8.5 | 5.3 | |
2.5×6 KU-L | 2.5 | 4.2 | 2.4 | 6.0 | 19.0 | 9.5 | 6.4 | |
4×4 KU-L | 4 | 6.0 | 3.5 | 8.0 | 17.5 | 8.0 | 4.3 | |
4×5 KU-L | 4 | 6.0 | 3.5 | 8.0 | 19.0 | 9.0 | 5.3 | |
4×6 KU-L | 4 | 6.0 | 3.5 | 8.0 | 18.5 | 11.0 | 6.4 | |
4×8 KU-L | 4 | 6.0 | 3.5 | 8.0 | 21.5 | 14.0 | 8.4 | |
6×5 KU-L | 6 | 3.0/2.75 | 6.5 | 3.5 | 9.0 | 21.0 | 11.4 | 5.0 |
6×6 KU-L | 6 | 3.0/2.75 | 6.5 | 3.5 | 9.0 | 21.5 | 11.4 | 6.0 |
6×8 KU-L | 6 | 3.0/2.75 | 6.5 | 3.5 | 9.0 | 23.0 | 13.0 | 8.0 |
6×10 KU-L | 6 | 3.0/2.75 | 6.5 | 3.5 | 9.0 | 25.0 | 16.0 | 10.0 |
10×6 KU-L | 10 | 4.1/3.55 | 7.0 | 4.5 | 10.0 | 22.0 | 11.5 | 6.0 |
10×8 KU-L | 10 | 4.1/3.55 | 7.0 | 4.5 | 10.0 | 23.5 | 14.5 | 8.0 |
10×10 KU-L | 10 | 4.1/3.55 | 7.0 | 4.5 | 10.0 | 26.5 | 18.0 | 10.0 |
10×12 KU-L | 10 | 4.1/3.55 | 7.0 | 4.5 | 10.0 | |||
16×6 KU-L | 16 | 5.1/4.50 | 8.5 | 5.5 | 12.0 | 26.0 | 13.0 | 6.0 |
16×8 KU-L | 16 | 5.1/4.50 | 8.5 | 5.5 | 12.0 | 26.0 | 14.0 | 8.0 |
16×10 KU-L | 16 | 5.1/4.50 | 8.5 | 5.5 | 12.0 | 29.0 | 17.0 | 10.0 |
16×12 KU-L | 16 | 5.1/4.50 | 8.5 | 5.5 | 12 | 30 | 20.0 | 13.0 |
25×6 KU-L | 25 | 6.3 (5.6-6.5 pagal VDE 0295) | 10.0 | 7.0 | 14 | 28 | 14.0 | 6.5 |
25×8 KU-L | 25 | 6.3 (5.6-6.5 pagal VDE 0295) | 10.0 | 7.0 | 14.0 | 30.0 | 16.0 | 8.0 |
25×10 KU-L | 25 | 6.3 (5.6-6.5 pagal VDE 0295) | 10.0 | 7.0 | 14.0 | 32.0 | 18.0 | 10.0 |
25×12 KU-L | 25 | 6.3 (5.6-6.5 pagal VDE 0295) | 10.0 | 7.0 | 14.0 | 20.0 | 20.0 | 13.0 |
35×6 KU-L | 35 | 7.5 (6.6-7.5 pagal VDE 0295) | 12.0 | 8.5 | 17 | 32 | 18.0 | 6.5 |
35×8 KU-L | 35 | 7.5 (6.6-7.5 pagal VDE 0295) | 12.0 | 8.5 | 17.0 | 32.0 | 18.0 | 8.0 |
35×10 KU-L | 35 | 7.5 (6.6-7.5 pagal VDE 0295) | 12.0 | 8.5 | 17.0 | 35.0 | 18.0 | 10.0 |
35×12 KU-L | 35 | 7.5 (6.6-7.5 pagal VDE 0295) | 12.0 | 8.5 | 17.0 | 37.0 | 21.0 | 13.0 |
50×8 KU-L | 50 | 9.0 (7.7-8.6 pagal VDE 0295) | 14.0 | 10.0 | 20.0 | 38.0 | 21.0 | 8.0 |
50×10 KU-L | 50 | 9.0 (7.7-8.6 pagal VDE 0295) | 14.0 | 10.0 | 20.0 | 39.0 | 21.0 | 10.0 |
50×12 KU-L | 50 | 9.0 (7.7-8.6 pagal VDE 0295) | 14.0 | 10.0 | 20.0 | 43.0 | 21.0 | 13.0 |
70×8 KU-L | 70 | 10.5 (9.3-10.2 pagal VDE 0295) | 16.5 | 12.0 | 21.0 | 41.0 | 22.0 | 8.0 |
70×10 KU-L | 70 | 10.5 (9.3-10.2 pagal VDE 0295) | 16.5 | 12.0 | 21.0 | 41.0 | 22.0 | 10.0 |
70×12 KU-L | 70 | 10.5 (9.3-10.2 pagal VDE 0295) | 16.5 | 12.0 | 21.0 | 41.0 | 22.0 | 13.0 |
95×8 KU-L | 95 | 12.5 (11.0-12.0 pagal VDE 0295) | 18.0 | 13.5 | 24.0 | 48.0 | 25.0 | 8.0 |
95×10 KU-L | 95 | 12.5 (11.0-12.0 pagal VDE 0295) | 18.0 | 13.5 | 24.0 | 48.0 | 25.0 | 10.0 |
95×12 KU-L | 95 | 12.5 (11.0-12.0 pagal VDE 0295) | 18.0 | 13.5 | 24.0 | 49.0 | 25.0 | 13.0 |
120×8 KU-L | 120 | 14.0 (12.5-13.5 pagal VDE 0295) | 19.5 | 15.0 | 26.0 | 52.0 | 29.0 | 8.0 |
120×10 KU-L | 120 | 14.0 (12.5-13.5 pagal VDE 0295) | 19.5 | 15.0 | 26.0 | 52.0 | 29.0 | 10.0 |
120×12 KU-L | 120 | 14.0 (12.5-13.5 pagal VDE 0295) | 19.5 | 15.0 | 26.0 | 52.0 | 29.0 | 13.0 |
150×10 KU-L | 150 | 15.7 (13.9-15.0 pagal VDE 0295) | 21.0 | 16.5 | 29.0 | 55.0 | 31.0 | 10.0 |
150×12 KU-L | 150 | 15.7 (13.9-15.0 pagal VDE 0295) | 21.0 | 16.5 | 29.0 | 55.0 | 31.0 | 13.0 |
150×16 KU-L | 150 | 15.7 (13.9-15.0 pagal VDE 0295) | 21.0 | 16.5 | 29.0 | 57.0 | 31.0 | 17.0 |
185×10 KU-L | 185 | 17.5 (15.8-16.8 pagal VDE 0295) | 24.0 | 19.0 | 30 | 65.0 | 35.0 | 10.5 |
185×12 KU-L | 185 | 17.5 (15.8-16.8 pagal VDE 0295) | 24.0 | 19.0 | 30 | 65 | 35 | 13.0 |
185×16 KU-L | 185 | 17.5 (15.8-16.8 pagal VDE 0295) | 24.0 | 19.0 | 30 | 65 | 35 | 17.0 |
240×12 KU-L | 240 | 17.8-19.2 | 26.0 | 21.0 | 35 | 76 | 38 | 13.0 |
240×16 KU-L | 240 | 17.8-19.2 | 26.0 | 21.0 | 35 | 72 | 38 | 17.0 |
Other sizes on request. This type of lug requires non-DIN special dies for pressing. Designations used: rm-round multi-conductor; sm-sector multi-conductor; re-conductor single-conductor round monolith; se-conductor single-conductor sector monolith.