Application: for Al conductors according to DIN 48201 and cable conductors with Al conductors according to VDE 0295.
Voltage: up to 36 kV;
Material: electrotechnical copper and aluminum;
Surface: uncoated.
Name | Conductor cross-section, mm² (rm/sm)/se | Conductor diameter, mm pagal VDE 0295 | Conductor diameter, mm pagal DIN48201/5 | Matrix code | d1xd2xl1xl2, mm | Number of clamping points (mech./hidr.) | 100 pcs. apx. weight kg |
---|---|---|---|---|---|---|---|
25 ALU-KU-PA | 25 | 5.6-6.7 | 6.3 | 12 | 6.8x6x58x20 | 4/2 | 1.6 |
35 ALU-KU-PA | 35 | 6.6-7.8 | 7.5 | 14 | 8.3x7x71x22 | 5/3 | 2.5 |
50 ALU-KU-PA | 50/70 | 7.7-9.4 | 9.0 | 16 | 10.0x874x25 | 5/3 | 3.3 |
70 ALU-KU-PA | 70/95 | 9.3-11.0 | 10.5 | 18 | 11.5x10x87x30 | 6/3 | 5.4 |
95 ALU-KU-PA | 95/120 | 11.0-12.4 | 12.5 | 22 | 13.2x12x91x33 | 6/3 | 8.7 |
120 ALU-KU-PA | 120/150 | 12.5-13.8 | 14.0 | 22 | 14.7x12x98x38 | 6/3 | 9.0 |
150 ALU-KU-PA | 150/185 | 13.9-15.0 | 15.7 | 25 | 16.3x12x108x38 | 7/3 | 10.9 |
185 ALU-KU-PA | 185/240 | 15.5-16.8 | 17.5 | 28 | 18.3x14x116x44 | /3 | 15.7 |
240 ALU-KU-PA | 240/300 | 17.8-19.2 | 20.3 | 32 | 21.0x16x128x44 | /3 | 21.8 |
300 ALU-KU-PA | 300 | 20.0-21.6 | 22.5 | 34 | 23.3x18x131x46 | /3 | 26.7 |
Other sizes on request. Conductors with a sector profile must be rounded before pressing. Tips are filled with a special contact paste and hermetically sealed in plastic.
Designations used: rm-round multi-conductor; sm-sector multi-conductor; re-conductor single-conductor round monolith; se-conductor single-conductor sector monolith.