Gerhard Petri Vilnius UAB

Nexans
e-paslaugos

Indoor and outdoor type end sleeves for three-core 6 and 10 kV cables with oil-paper tape insulation (MI and MIND) and common metal sheath

Cable

The internal type end sleeve is designed for 6 and 10 kV three-conductor cables with oil-paper tape insulation (MI, MIND) and common aluminum or lead sheath.
Ex: AABU, ACBU.

End sleeve design

Oil-resistant Thermo shrink tubing is planted on the paper-insulated cable cores. The root of the cable shall be filled with yellow oil-resistant mastic and sealed with a conductive glove with an adhesive coating on the inner surface. This glove shall be mounted on the end of the cores and the metallic sheath. Yellow electric field control mastic shall be wrapped around the fingertips of the glove and red trekking-resistant tubing shall be planted on the veins. An additional sealing tube seals the back of the sleeve, whether a tip is used or a monolithic conductor is retained. The rear coupling shall include a non-solderable earth fitting. The kits with modification code -L12 shall include bolted lugs with a bore diameter suitable for M12 bolts and -L16 for M16 bolts.




    Internal type end sleeves for three-core 6 and 10 kV cables with oil-paper tape insulation (MI and MIND) and a common metallic sheath

    Rated voltage Uo/U (kV) Cross-section of the cores (mm²) Product code for ordering Dimension (mm)
    L
    Without lugs With screw lugs*
    3,5/6 ir 6/10 25-50 GUST 12/ 25- 50/ 450 GUST 12/ 25- 50/ 450-L12 450
    GUST 12/ 25- 50/ 800 GUST 12/ 25- 50/ 800-L12 800
    GUST 12/ 25- 50/1200 GUST 12/ 25- 50/1200-L12 1200
    70-120 GUST 12/ 70-120/ 450 GUST 12/ 70-120/ 450-L12 450
    GUST 12/ 70-120/ 800 GUST 12/ 70-120/ 800-L12 800
    GUST 12/ 70-120/1200 GUST 12/ 70-120/1200-L12 1200
    150-240 GUST 12/150-240/ 450 GUST 12/150-240/ 450-L12 450
    GUST 12/150-240/ 800 GUST 12/150-240/ 800-L12 800
    GUST 12/150-240/1200 GUST 12/150-240/1200-L12 1200

    * To order a rear coupling with bolt lugs for M16 bolts, use -L16 instead of modification code -L12.

    Note: One set of couplings includes materials for 3 phases. Only sealed cable lugs can be used. The lengths of the cores can be reduced at the installation site according to local requirements, with a minimum length of 450 mm.

    Outdoor-type end sleeves for three-core 6 and 10 kV cables with oil-paper tape insulation (MI and MIND) and a common metallic sheath

    Rated voltage Uo/U (kV) Cross-section of the cores (mm²) Product code for ordering Dimension (mm)
    L
    Without lugs With screw lugs*
    3,5/6 25-50 GUST 12/ 25- 50/ 450 GUST 12/ 25- 50/ 450-L12 450
    GUST 12/ 25- 50/ 800 GUST 12/ 25- 50/ 800-L12 800
    GUST 12/ 25- 50/1200 GUST 12/ 25- 50/1200-L12 1200
    70-120 GUST 12/ 70-120/ 450 GUST 12/ 70-120/ 450-L12 450
    GUST 12/ 70-120/ 800 GUST 12/ 70-120/ 800-L12 800
    GUST 12/ 70-120/1200 GUST 12/ 70-120/1200-L12 1200
    150-240 GUST 12/150-240/ 450 GUST 12/150-240/ 450-L12 450
    GUST 12/150-240/ 800 GUST 12/150-240/ 800-L12 800
    GUST 12/150-240/1200 GUST 12/150-240/1200-L12 1200
    6/10 25-50 GUST 12/ 25- 50/ 800 GUST 12/ 25- 50/ 800-L12 800
    GUST 12/ 25- 50/1200 GUST 12/ 25- 50/1200-L12 1200
    70-120 GUST 12/ 70-120/ 800 GUST 12/ 70-120/ 800-L12 800
    GUST 12/ 70-120/1200 GUST 12/ 70-120/1200-L12 1200
    150-240 GUST 12/150-240/ 800 GUST 12/150-240/ 800-L12 800
    GUST 12/150-240/1200 GUST 12/150-240/1200-L12 1200

    * To order a rear coupling with bolt lugs for M16 bolts, use -L16 instead of modification code -L12.

    Note: One set of couplings includes materials for 3 phases. Only sealed cable lugs can be used. The lengths of the cores can be reduced on-site according to local requirements, the minimum length of the cores being 450 mm for Uo/U= 3,5/6 kV and 800 mm for Uo/U= 6/10 kV.