Gerhard Petri Vilnius UAB

Nexans
e-paslaugos

Hermetic press-fit lugs ALU-F (rod), DIN 46329

Application: cable lugs for wet rooms and outdoor applications. For Al conductors according to DIN 48201 and Al cable strands according to VDE 0295.
Voltage: up to 36 kV;
Material: Al 99.5;
Surface:
ALU-F: uncoated;
ALU-F-V: electrochemically tin-plated (20 μm thick coating).




    Name Conductor cross-section, mm² (rm/sm)/se Conductor diameter, mm (According to VDE 0295/According to DIN 48201/5) Matrix code D/d, mm l/b, mm Fixing screw M Number of clamping points (mech./hidraul.)
    16×8 ALU-F 16/25 5.2-5.6/5.1 12 12.0/5.4 50/20 8.0 4/2
    16×10 ALU-F 16/25 5.2-5.6/5.1 12 12.0/5.4  50/25  10.0  4/2
    25×8 ALU-F 25/35 5.6-6.7/6.3 12 12.0/6.8 50/20 8.0 4/2
    25×10 ALU-F 25/35 5.6-6.7/6.3 12 12.0/6.8  50/25  10.0  4/2
    25×12 ALU-F 25/35 5.6-6.7/6.3 12 12.0/6.8  50/25  13.0  4/2
    35×8 ALU-F 35/50 6.6-7.8/7.5 14 14.0/8.0 62/25 8.0 5/2
    35×10 ALU-F 35/50 6.6-7.8/7.5 14 14.0/8.0  62/25  10.0  5/2
    35×12 ALU-F 35/50 6.6-7.8/7.5 14 14.0/8.0  62/25  13.0  5/2
    50×8 ALU-F 50/70 7.7-9.4/9.0 16 16.0/9.8 62/25 8.0 5/2
    50×10 ALU-F 50/70 7.7-9.4/9.0 16 16.0/9.8  62/25  10.0  5/2
    50×12 ALU-F 50/70 7.7-9.4/9.0 16 16.0/9.8  62/25  13.0  5/2
    70×10 ALU-F 70/95 9.3-11.0/10.5 18 18.5/11.2 72/25 10.5 6/3
    70×12 ALU-F 70/95 9.3-11.0/10.5 18 8.5/11.2  72/25  13.0  6/3
    95×10 ALU-F 95/120 11.0-12.4/12.5 22 22.0/13.2 78/25 10.0 6/3
    95×12 ALU-F 95/120 11.0-12.4/12.5 22 22.0/13.2  75/25  13.0  6/3
    120×10 ALU-F 120/150 12.5-13.8/14.0 22 23.0/14.7 84/30 10.0 6/3
    120×12 ALU-F  120/150 12.5-13.8/14.0 22 23.0/14.7 80/30  13.0  6/3
    120×16 ALU-F 120/150 12.5-13.8/14.0 22 23.0/14.7  80/30  17.0  6/3
    150×10 ALU-F 150/185 13.9-15.0/15.7 25 25.0/16.3 90/30 10.0 6/3
    150×12 ALU-F 15/185 13.9-15.0/15.7 25 25.0/16.3  90/30  13.0  6/3
    150×16 ALU-F 150/185 13.9-15.0/15.7 25 25.0/16.3  90/30  17.0  6/3
    185×10 ALU-F 185/240 15.5-16.8/17.5 28 28.5/18.3 91/30 10.0 6/3
    185×12 ALU-F 185/240 15.5-16.8/17.5 28 28.5/18.3  91/30  13.0  6/3
    185×16 ALU-F 185/240 15.5-16.8/17.5 28 28.5/18.3  91/30  17.0  6/3
    185×20 ALU-F 185/240 15.5-16.8/17.5 28 28.5/18.3  91/38  21.0  6/3
    240×10 ALU-F 240/300 17.8-19.2/20.3 32 32.0/21.0 103/38 10.0 8/3
    240×12 ALU-F 240/300 17.8-19.2/20.3 32 32.0/21.0  103/38  13.0  8/3
    240×16 ALU-F 240/300 17.8-19.2/20.3 32 32.0/21.0  103/38  17.0  8/3
    240×20 ALU-F 240/300 17.8-19.2/20.3 32 32.0/21.0  103/38  21.0  8/3
    300×12 ALU-F 300 20.0-21.6/22.5 34 34.0/23.3 103/38 13.0 8/3
    300×16 ALU-F 300 20.0-21.6/22.5 34 34.0/23.3  103/38  17.0  8/3
    400×12 ALU-F 400 22.9-24.6 38 38.5/26.0 116/38 13.0 -/3
    500×12 ALU-F 500 25.7-27.6 44 44.0/29.0 122/44 13.0 -/4
    500×16 ALU-F 500 25.7-27.6 44 44.0/29.0  122/44  17.0  -/4

    Please enquire further about other nozzle sizes and ALU-F-V (tin-plated) nozzles. Cable lugs are filled with special contact paste and hermetically sealed in plastic.
    Designations used: rm-round multicore conductor; sm-sector multicore conductor; re-conductor single-wire round monolith; se-conductor single-wire sector monolith.

    Panašios prekės