Types:
KZEP, P2X, P4X, P3X;
KZ2-150-2B;
KZ31.
Purpose and technical characteristics:
1. KZEP, P2X, P4X, P3X
These hermetically sealed insulation-piercing branch circuits
terminals are suitable for all types of low-voltage insulated air
lines, as well as inlets and street lighting
cables.
When tightening the screws, the teeth of the contact blades cut through
the insulation and ensures excellent contact with the core
This avoids stripping of the wire insulation.
The screws are tightened until their heads are broken off.
2. KZ2-150-2B
Suitable for aluminum and copper wires;
13 mm long-necked screw with a breakaway head
ensures reliable installation;
The screws are insulated against live contact
blades, so that the terminal can be safely installed without disconnecting
The clamp can be removed without removing the voltage;
Hermeticity tested in a water bath at 6 kV
for 30 minutes;
Exceeds the requirements of NFC 33020 and EATS 43-14 standards.
3. KZ31
No drop-out components, rear cap
attached to the housing;
Insulating material made of weatherproofing
and UV-resistant, glass fiber reinforced
polymer;
The contact blades shall be made of aluminum or copper and
the screws shall be made of specially machined steel.
Name | Conductor cross-section (mm²)-main | Conductor cross-section (mm²) – branch | Screws | Moment, Nm | Weight, kg/100 pcs. | Note |
---|---|---|---|---|---|---|
KZEP-13* | 16-95 | 1.5-10 | 1xM6 | 7 | 5.0 | for connecting the branch cable to the main |
P2X-95* | 16-95 | 4-35(50^) | 1xM8 | 11 | 12.0 | for connecting the branch cable to the main |
P2X-150* | 50-150 | 6-35(50^) | 1xM8 | 11 | 12.0 | for connecting the branch cable to the main |
P3X-95* | 25-95 | 25-95 | 1xM8 | 18 | 16.0 | for connecting the main cables |
P4X-150D | 50-150 | 50-150 | 2xM8 | 22 | 20.0 | for connecting the main cables |
KZ4-185* | 70-185 | 70-185 | 1xM10 | 22 | 20.0 | for connecting the main cables |
KZ2-150 2B** | 25-150 | 2×6-35 | 3xM8 | 11/10 | 23.0 | For connecting 2 branch wires to the main (pre-insulated) |
KZ2-150 2Bp** | 25-150 | 2×6-35 | 3xM8 | 11/10 | 23.0 | 2 branch wires for connection to the main (piercing the insulation) |
KZ31-70/70** | 35-70 | 35-70(95^^) | 1xM8/1xM10 | 18/10 | 24.0 | for connecting the main wires (branching by pre-insulating) |
KZ31-150/70** | 50-150 | 35-70(95^^) | 1xM8/1xM10 | 18/10 | 24.0 | for connecting the main wires (branching by pre-insulating) |
Other sizes on request.
TAGS:
*Terminal clamps where the main and branch wires are connected at the same time. **Independent-connection branch clamps where the main lead is connected by piercing the insulation and the insulation of the branch lead must be removed beforehand.
^ Suitable for cables up to this cross-section, but the maximum terminal current Imaks(138A in accordance with HD626S1 Part 6E) is less than the permissible maximum currents for overhead cables of this cross-section.
^^ Suitable for wires up to this cross-section, but the maximum terminal current Imaks (213A in accordance with HD626S1 Part 6E) is less than the permissible maximum overhead currents for this cross-section.
! Terminals where the branch line is connected by pre-insulating the wire shall have the possibility of disconnecting and reconnecting the branch line without disconnecting the main line.